Fire Sprinkler Head CAD Blocks

Pendant, upright and sidewall fire-sprinkler head CAD blocks - three physically different heads, not one symbol rotated three ways. Which one gets drawn follows the ceiling: pendant below a finished ceiling, upright on exposed pipe, sidewall where a run cannot cross the space. All three download as DXF, drawn to scale in inches.

3 blocks, 3 downloads on this page. DXF R2018, drawn in inches. Free, no signup.

Fire-Sprinkler Pendant Head 9in x 9in
Download Fire-Sprinkler Pendant Head Open in editor

DWG (R2000, converted from the DXF). PNG is the plan-view preview.

Fire-Sprinkler Pendant Head - plan view, 9in x 9in
Fire-Sprinkler Pendant Head - plan view, 9in x 9in

Fire-Sprinkler Pendant Head

Fire Sprinkler (MEP) - datum: pipe-connection point = head center (0,0) - default footprint 9in x 9in

Fire-Sprinkler Pendant Head - plan view CAD block
Fire-Sprinkler Pendant Head - plan view, 9in x 9in

The head hanging below a finished ceiling on a drop off the branch line above. Default wherever there is a ceiling to hide pipe in - offices, corridors, retail, guest rooms - and where it lands is as much an architectural decision as a fire protection one, because it sits in the tile grid.

Sizing

r, 2 to 6in, scales the symbol only, with cross arms at 1.5r for a 9 x 9in footprint at the 3in default. No real head varies that way; set r once so the sheet plots legibly. The governing numbers are protection area and spacing from NFPA 13 by hazard: up to 225 sq ft per sprinkler at 15ft spacing in light hazard under unobstructed construction, 130 sq ft at 15ft in ordinary, 100 sq ft at 12ft in extra hazard.

Drafting notes

Filled circle with a cross here against the open circle on the upright, so check the legend before assuming. The fill is an outer circle plus six concentric rings rather than a hatch: solid at plot scale, visibly ringed if you blow the block up. Connection point is the head center, so it snaps to a tile center. A pendant on a dry or preaction system has to be a dry pendant or the drop holds water.

Drawn alongside

Coordinated on the reflected ceiling plan against lights, diffusers and dome cameras, usually the last thing placed and the first thing moved. The branch feeding its drop belongs on the piping layer, not the ceiling sheet.

Dimensions

Plan footprint (W x H)9in x 9in
Unitsinches
DXF versionR2018
Insertion datumpipe-connection point = head center (0,0)

Parameters

ParameterDefaultRange / options
Radius3in2in–6in

Download

Relevant standards

NFPA 13 Standard for the Installation of Sprinkler Systems
Fixes protection area and maximum spacing per sprinkler by hazard classification, holds a standard spray deflector 1in to 12in below a smooth flat ceiling, keeps no sprinkler further from a wall than half the allowable spacing, and requires at least 6ft between adjacent sprinklers unless they are baffled.
UL 199
Automatic Sprinklers for Fire-Protection Service. A sprinkler is listed with the escutcheon or cover plate it was tested with, which is why recessed and concealed pendants are distinct products rather than trim options.

Fire-Sprinkler Upright Head

Fire Sprinkler (MEP) - datum: pipe-connection point = head center (0,0) - default footprint 9in x 9in

Fire-Sprinkler Upright Head - plan view CAD block
Fire-Sprinkler Upright Head - plan view, 9in x 9in

Deflector up, sitting above the branch line, for spaces with no finished ceiling: warehouse, parking garage, mechanical room, the underside of a deck. It is what you use when the pipe itself would stand in a pendant's spray pattern, and what a dry system needs so the branch drains.

Sizing

r, 2 to 6in, cross arms at 1.5r, 9 x 9in at default - geometrically identical to the pendant block, so open versus filled circle is the entire distinction and symbol size says nothing about the product. Where uprights change a layout is overhead: the NFPA 13 obstruction rules want roughly three times the obstruction's dimension of clearance, capped at 24in, from anything sitting below the deflector.

Drafting notes

Open circle with a cross, connection at head center - and that center rides on the branch line itself rather than the bottom of a drop, which is why uprights plot right on the pipe while pendants do not. Upright and pendant are separately listed and neither may be inverted, so a head drawn upright has to be scheduled upright.

Drawn alongside

Sits directly on the run blocks, so here the piping layout and the head layout are one geometry. Checked against structure, duct and high-bay lighting in the coordination model, since deflector clearance is what actually moves them.

Dimensions

Plan footprint (W x H)9in x 9in
Unitsinches
DXF versionR2018
Insertion datumpipe-connection point = head center (0,0)

Parameters

ParameterDefaultRange / options
Radius3in2in–6in

Download

Relevant standards

NFPA 13 Standard for the Installation of Sprinkler Systems
Its obstruction rules govern exposed installations, setting the clearance a standard spray sprinkler needs from anything below the deflector and the deflector position relative to the branch line it sits on.
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
Exposed uprights are the ones that get painted, loaded with dust or struck by material handling, and each of those makes a sprinkler a replacement item rather than a cleaning item.

Fire-Sprinkler Sidewall Head

Fire Sprinkler (MEP) - datum: wall-connection point on wall line (0,0); throws +Y - default footprint 9.6in x 4.8in

Fire-Sprinkler Sidewall Head - plan view CAD block
Fire-Sprinkler Sidewall Head - plan view, 9.6in x 4.8in

The head that throws horizontally off a wall instead of down from a ceiling. It answers the case with nowhere to hide pipe: a flat slab soffit, an existing building with no plenum, a corridor or closet where running a branch across the space is not worth the coordination.

Sizing

r, 2 to 6in, draws a semicircle over a wall tick with a throw line into +Y, so unlike the round head symbols this one is asymmetric - 9.6 x 4.8in at default, about half the height of the pendant and upright blocks. That asymmetry is the information: the plan shows which way it sprays. Coverage limits are tighter than the pendant and upright allowances, and standard sidewall spray sprinklers are essentially a light hazard, smooth flat ceiling proposition.

Drafting notes

The wall connection point is at origin on the wall line with the throw into +Y, so the block mirrors and rotates onto any wall and still reads correctly. The deflector window is the tight one: NFPA 13 puts a sidewall 4in to 6in below the ceiling against 1in to 12in for a pendant, which turns soffits, valances and deep light coves from aesthetic details into obstructions.

Drawn alongside

Drawn with the branch line running along the wall or down the corridor rather than out across the room. Checked against door swings, upper cabinets and window treatments - anything in the throw is an obstruction a ceiling layout never argues about.

Dimensions

Plan footprint (W x H)9.6in x 4.8in
Unitsinches
DXF versionR2018
Insertion datumwall-connection point on wall line (0,0); throws +Y

Parameters

ParameterDefaultRange / options
Radius3in2in–6in

Download

Relevant standards

NFPA 13 Standard for the Installation of Sprinkler Systems
Places a standard sidewall deflector 4in to 6in below the ceiling and limits standard sidewall spray sprinklers to light hazard occupancies with smooth flat ceilings unless a specific listing says otherwise.

Standards are listed for drafting context only. A symbol drawn to a convention is not a compliance determination - verify against the governing code and the specified product. See the license and terms.

Related families

All 33 block families

Sprinkler heads, ready to place.

Device symbols for the fire protection sheet. Open one in the editor or take the DXF.

Whole library

Get the entire library - all 219 blocks as one ZIP

Every category, every MEP orientation, DXF R2018, sorted into folders. Tell us where to send it and the download starts immediately.

One email, when there is something worth telling you. No spam, ever. Prefer not to? Take the ZIP without giving an email.