Block family

Eyewash Station and Safety Shower CAD Blocks

Emergency eyewash station, emergency safety shower and the combination unit that does both - three life-safety CAD blocks that get located by travel distance rather than by fitting the wall. Footprints run 16x14in to 22x22in, small symbols whose placement carries the weight. Free DXF downloads, drawn to scale in inches.

3 blocks, 3 downloads on this page. DXF R2018, drawn in inches. Free, no signup.

Emergency Eyewash Station 16in x 14in
Download Emergency Eyewash Station Open in editor

DWG (R2000, converted from the DXF). PNG is the plan-view preview.

Emergency Eyewash Station - plan view, 16in x 14in
Emergency Eyewash Station - plan view, 16in x 14in

Emergency Eyewash Station

Commercial Safety - datum: near-left corner - default footprint 16in x 14in

Emergency Eyewash Station - plan view CAD block
Emergency Eyewash Station - plan view, 16in x 14in

Two-spray flushing station for the eyes and face. Bench and wall-mount units go in labs, clean rooms, print areas and machine shops. It appears on the plumbing plan for supply and tailpiece and again on the casework plan, because it takes counter frontage away from the work.

Sizing

16 x 14 in is a bowl-and-nozzle bench unit. The 12 to 20 in width runs from a compact wall-mount up to a full stainless bowl. The 10 to 18 in depth is projection off the counter back, which is the number that decides whether the aisle behind still works.

Drafting notes

Origin at the near-left corner means the block lines up with the end of a casework run directly. Draw the bowl on the plumbing fixture layer, then dash the clear approach path on the life-safety layer: the approach is what gets argued about in review, not the footprint.

Drawn alongside

Paired with the drench shower where one hazard can reach both the eyes and the body, and with the thermostatic mixing valve that tempers its supply, since that valve needs its own space and its own tag.

Dimensions

Plan footprint (W x H)16in x 14in
Unitsinches
DXF versionR2018
Insertion datumnear-left corner

Parameters

ParameterDefaultRange / options
Width16in12in–20in
Depth14in10in–18in

Download

Relevant standards

ANSI/ISEA Z358.1
Covers eyewash performance: the 15-minute flushing duration, the nozzle height range above the floor, a clear path from the hazard, and tepid flushing fluid between 60 and 100 degrees F.
OSHA 29 CFR 1910.151(c)
The federal requirement for suitable eye-flushing facilities within the work area wherever eyes may be exposed to injurious corrosive materials.

Emergency Safety Shower

Commercial Safety - datum: near-left corner of reach footprint - default footprint 20in x 20in

Emergency Safety Shower - plan view CAD block
Emergency Safety Shower - plan view, 20in x 20in

Overhead drench shower for whole-body chemical exposure: plating lines, battery rooms, water treatment, chemical decanting. It lands on the plumbing plan for supply and drainage and again on the architectural plan, because the clear floor area under the head is space no one gets to use.

Sizing

The circle is the spray and reach footprint, not the shower head. The 20 in default is the minimum spray-pattern diameter ANSI/ISEA Z358.1 describes at 60 in above the standing surface. The standard also keeps the center of that pattern at least 16 in clear of any obstruction, so the 28 in end of the range is a plan reservation rather than a product size.

Drafting notes

The origin is the near-left corner of the reach footprint rather than the pipe centerline, which lets the circle snap against a wall face or column grid line while the drop stays where the plumbing engineer wants it. Keep the unit on the same floor level as the hazard it serves; one reached across a stair, a ramp or a door swing will not survive review.

Drawn alongside

Drawn with the eyewash it backs up and with the floor drain or containment that has to handle a 20 gpm flow for a sustained flush.

Dimensions

Plan footprint (W x H)20in x 20in
Unitsinches
DXF versionR2018
Insertion datumnear-left corner of reach footprint

Parameters

ParameterDefaultRange / options
Diameter20in16in–28in

Download

Relevant standards

ANSI/ISEA Z358.1
The consensus standard for emergency shower performance, covering spray-pattern size at 60 in, flow rate, the 15-minute flushing duration and the ten-second reach convention from the hazard.
OSHA 29 CFR 1910.151(c)
Requires suitable facilities for quick drenching or flushing of the body within the work area where a person may be exposed to injurious corrosive materials. It states no dimensions; OSHA looks to Z358.1 for those.

Combination Eyewash and Safety Shower

Commercial Safety - datum: near-left corner of reach footprint - default footprint 22in x 22in

Combination Eyewash and Safety Shower - plan view CAD block
Combination Eyewash and Safety Shower - plan view, 22in x 22in

Combination unit on a single supply: a drench head overhead with an eyewash bowl on the same stanchion. It is the default where one hazard can reach eyes and body both and running one water line beats running two. Common on plating rooms and mixing platforms.

Sizing

The 22 in default circle is wider than the standalone shower's 20 in because the eyewash bowl swings out into the same footprint. Stay near 18 in for a folding-bowl wall-mount combo; the 30 in end is a free-standing stanchion with a bowl that sits extended.

Drafting notes

One symbol stands for two devices, so tag it explicitly. A schedule that reads only eyewash against this block gets the wrong fixture ordered, and that error survives all the way to submittal. The footprint is set from its near-left corner, which keeps the circle referenced to building geometry instead of to the riser.

Drawn alongside

It replaces the separate eyewash and shower blocks rather than joining them. If all three appear in one room, one of them is a leftover from an earlier layout.

Dimensions

Plan footprint (W x H)22in x 22in
Unitsinches
DXF versionR2018
Insertion datumnear-left corner of reach footprint

Parameters

ParameterDefaultRange / options
Diameter22in18in–30in

Download

Relevant standards

ANSI/ISEA Z358.1
Treats combination units as their own equipment class, with the shower and eyewash components each judged against their own performance requirements.
OSHA 29 CFR 1910.151(c)
The underlying federal requirement covering both cases: quick drenching and flushing facilities within the work area.

Standards are listed for drafting context only. A symbol drawn to a convention is not a compliance determination - verify against the governing code and the specified product. See the license and terms.

Related families

All 33 block families

Life-safety fixtures, ready to place.

Eyewash and shower stations for the safety plan. Open one in the editor or take the DXF.

Whole library

Get the entire library - all 219 blocks as one ZIP

Every category, every MEP orientation, DXF R2018, sorted into folders. Tell us where to send it and the download starts immediately.