Block family

Fire Alarm and Extinguisher CAD Blocks

Fire alarm pull station, smoke and CO detector, and the fire extinguisher cabinet - three fire-protection CAD blocks that live on the device plan rather than the sprinkler sheet. The cabinet is the only one with a real footprint at 12x8in; the two devices are wall and ceiling symbols. All three download as DXF.

3 blocks, 3 downloads on this page. DXF R2018, drawn in inches. Free, no signup.

Fire Alarm Pull Station 8in x 8in
Download Fire Alarm Pull Station Open in editor

DWG (R2000, converted from the DXF). PNG is the plan-view preview.

Fire Alarm Pull Station - plan view, 8in x 8in
Fire Alarm Pull Station - plan view, 8in x 8in

Fire Alarm Pull Station

Commercial Safety - datum: wall-mount point on wall line - default footprint 8in x 8in

Fire Alarm Pull Station - plan view CAD block
Fire Alarm Pull Station - plan view, 8in x 8in

Manual fire alarm box. It is the occupant-initiated device on the system, so it counts as an initiating device alongside detectors but is scheduled and circuited apart from horns and strobes. Drawn at exits and at stair discharges.

Sizing

The symbol is a circle, 4 in radius by default for an 8 in footprint. That is symbol size and not product size, since a real pull station is smaller than the circle. Work the 3 to 6 in radius against plot scale so the marker stays legible at 1/8 in without swallowing the door tag beside it.

Drafting notes

The datum sits on the wall line, so the circle centers off the wall face and reads as a wall device rather than a floor item. Keep pull stations on an initiating-device layer separate from notification appliances; that one split is what makes an accurate device count possible at bid time.

Drawn alongside

Drawn near the exit door and the sign above it, since all three mark the same egress point and have to move as a group when a door location shifts.

Dimensions

Plan footprint (W x H)8in x 8in
Unitsinches
DXF versionR2018
Insertion datumwall-mount point on wall line

Parameters

ParameterDefaultRange / options
Radius4in3in–6in

Download

Relevant standards

NFPA 72 National Fire Alarm and Signaling Code
Governs manual fire alarm box placement and spacing, and puts the operable part between 42 in and 48 in above the finished floor.
ADA 2010 Standards
Section 308 caps an unobstructed reach at 48 in above the floor, which is the ceiling the NFPA 72 mounting range was aligned to.

Fire Extinguisher Cabinet

Commercial Safety - datum: wall-mount point on wall line - default footprint 12in x 8in

Fire Extinguisher Cabinet - plan view CAD block
Fire Extinguisher Cabinet - plan view, 12in x 8in

Recessed or semi-recessed cabinet housing a portable extinguisher, drawn on the architectural plan and picked up again on the life-safety coverage diagram. The wall type it lands in decides whether it can recess at all, which makes it a partition question before it is a fire-protection question.

Sizing

12 x 8 in suits a cabinet sized for a 10 lb ABC extinguisher; the 9 to 16 in width roughly brackets a 5 lb unit up to a 20 lb one. Depth is the number that causes trouble: a nominal 2x4 partition gives about 4-3/4 in of wall thickness, so nothing in the 6 to 10 in range fully recesses into one.

Drafting notes

With the datum on the wall line, depth runs into the wall for a recessed cabinet; mirror the block instead of rotating it when the unit is surface-mounted and projects into the room. Carry the mounting condition as an attribute, because recessed and surface versions of the same cabinet are different part numbers.

Drawn alongside

Checked against the travel-distance circles on the life-safety plan and against door swings, since a cabinet wants the same stretch of wall that everything else near an exit wants.

Dimensions

Plan footprint (W x H)12in x 8in
Unitsinches
DXF versionR2018
Insertion datumwall-mount point on wall line

Parameters

ParameterDefaultRange / options
Width12in9in–16in
Depth8in6in–10in

Download

Relevant standards

NFPA 10 Standard for Portable Fire Extinguishers
Sets the 75 ft maximum travel distance for Class A hazards, which is what determines how many cabinets a floor plate needs and roughly where they land.
ADA 2010 Standards
Section 307.2 limits an object with its leading edge between 27 in and 80 in above the floor to 4 in of protrusion into a circulation path, which is why corridor cabinets are usually recessed or semi-recessed.

Smoke / CO Detector

Residential Mechanical / Electrical - datum: device center (ceiling) - default footprint 6in x 8.01in

Smoke / CO Detector - plan view CAD block
Smoke / CO Detector - plan view, 6in x 8.01in

Ceiling-mounted smoke or combination smoke/CO device for residential and light commercial electrical plans and RCPs. The device count and locations are set by the code edition in force; the symbol usually carries a suffix distinguishing smoke-only from combination units.

Sizing

The 6in default diameter reflects a typical detector base; the 5-8in range covers residential and commercial bases alike. Note the 6in x 8in bbox is taller than the base is wide, so the symbol carries geometry beyond the plain circle.

Drafting notes

Device center at the ceiling is the datum, matching the ceiling fan block so both coordinate on the same reflected ceiling grid. Conventionally drawn on a fire alarm or low-voltage layer rather than with the general power devices.

Drawn alongside

Drawn with the ceiling fan and other ceiling-mounted devices on the RCP, and with the thermostat on the residential electrical sheet.

Dimensions

Plan footprint (W x H)6in x 8.01in
Unitsinches
DXF versionR2018
Insertion datumdevice center (ceiling)

Parameters

ParameterDefaultRange / options
Diameter6in5in–8in

Download

Relevant standards

NFPA 72
National Fire Alarm and Signaling Code - detector spacing and location, with household alarms in Chapter 29 and commercial initiating devices in Chapter 17. Carbon monoxide provisions moved into NFPA 72 with the 2019 edition when NFPA 720 was withdrawn, so legacy specs citing NFPA 720 are pointing at a retired document.

Standards are listed for drafting context only. A symbol drawn to a convention is not a compliance determination - verify against the governing code and the specified product. See the license and terms.

Related families

All 33 block families

Fire protection devices, ready to place.

Pull stations, detectors and cabinets for the device plan. Open one in the editor or take the DXF.

Whole library

Get the entire library - all 219 blocks as one ZIP

Every category, every MEP orientation, DXF R2018, sorted into folders. Tell us where to send it and the download starts immediately.

One email, when there is something worth telling you. No spam, ever. Prefer not to? Take the ZIP without giving an email.